Testing Power Rail Sequences in Complex Embedded Systems

This guide explains how to measure and validate power rail sequencing in embedded systems to ensure proper startup timing and long-term reliability.

Testing Power Rail Sequences in Complex Embedded Systems
Figure 1. Four power rail signals on a single grid, with cursors measuring the time delay between the first pair in the sequence.

Embedded computing systems generally require multiple supply voltages to deliver power to the microprocessor, memory and other on-board devices. There is usually a 12- or 15-volt DC primary supply, and numerous buck or boost converters working off the primary to help provide various voltages throughout the embedded system. Most microcontrollers have a prescribed order in which the voltages must be applied to prevent problems like lockups, so an area of concern when designing deeply embedded systems is the proper sequencing of power rails as they power up or down. Power management IC’s (PMIC) or power sequencers perform many of the sequencing tasks, but during validation and when troubleshooting, the order and timing of the power sequence should be verified.

Power rail sequence verification is a straightforward test. Connect the oscilloscope probes to each supply rail with the device under test powered off. Set the oscilloscope to trigger on the primary supply, with all traces overlapping on a single grid. The number of rails in your system and the length of time it takes for the sequence to complete determines the number of channels and memory length required, since every rail in a dependent sequence should be probed in a single acquisition. Our 8-channel, 5 Gpts WaveRunner 8000HD oscilloscopes are ideal for this task.

Figure 1 shows an acquisition made on an embedded system with 5 V, 3.3 V, 13 V and -12 V power rails. Triggering in this case was referenced to the -12 V bus, which was the last to come on. Note that in Figure 1, the traces have been displayed on the same grid to clearly show the sequence, with offset added to the Z1(C1) trace so that it overlaps the others. The “on” time for each trace is the point at which it reaches its minimum effective voltage. For C1, that occurs around 10 ms.

What is expected is that the voltage levels should rise or fall monotonically in the desired order at the desired time intervals. In this example, the 13 V rail (magenta trace) turns on before the others, followed by the 5 V rail (green trace), then the 3.3 V rail (blue trace) and finally the -12 V rail (yellow trace). The time delay between each power rail coming on is measured with cursors. Figure 1 shows the delay between the first pair of 13 V and 5 V buses measured at 5.18 ms. Measuring the delta from the previous rails is repeated for each rail in sequence.

Figure 2: The Dtime@level parameter automatically measures the delay between the 13 V rail (Z2) and the -12 V rail (Z1).

In the real world, embedded systems don't turn on just once. They are turned on and off multiple times, perhaps many thousands of times over the life cycle of the product, so a robust rail sequence must be able to maintain the proper order and delay over many power on cycles. Whereas a cursor measurement will verify a single sequence, the oscilloscope’s Parameter Compare Pass/Fail test capability will enable you to do some reliability testing.

The Pass/Fail setup begins with setting up the parameters that will used as the basis for comparison. For this test, configure a parameter using delta time at level (Dtime@level), which measures the time difference between two traces at a selected voltage threshold and slope. The last measurement on traces Z1 and Z2 is 17.4 ms, shown in the Measure table under P1 (click on the image to expand it).

Figure 3: Composite screen showing the setup of a Parameter Compare Pass/Fail test.

The next step is to setup a Pass/Fail test that compares the measured delta between Z2 coming on and Z1 coming on to an upper limit of 20 ms, as shown in the composite image in Figure 3. The Action dialog specifies that the device “Passes if…” Q1 is All True— that is, all P1 Dtime@level values are measured at less than 20 ms, meaning the -12 V rail always comes on within 20 ms of the 13 V rail before it. If a measured value fails the test (Dtime@level is greater than 20 ms), then the oscilloscope action is to stop the acquisition and hold the failed test on screen for inspection. It also generates a LabNotebook report, which saves all the data and measurements for further analysis.

Copyright © 2020-2026 Teledyne LeCroy. All rights reserved. All original content, including text and photos, is the property of Teledyne LeCroy and cannot be reproduced without expressed written permission.


William Kaunds presented a webinar 4 Practical Real-World Examples of Embedded System Validation and Debug which was Part 3 of the How to Efficiently Debug Embedded Systems With Your Oscilloscope webinar series. That webinar covers more details on this topic. Click the button below to watch this webinar or any of the other webinars in this series. Or download the transcript to preview the webinar content.

Great! You’ve successfully signed up.

Welcome back! You've successfully signed in.

You've successfully subscribed to Teledyne LeCroy Oscilloscope Blog.

Success! Check your email for magic link to sign-in.

Success! Your billing info has been updated.

Your billing was not updated.